How to Deal with the High Temperature Alarm of the Chiller?
The high temperature alarm of the chiller will cause the device to trigger the protection switch to be disconnected and cannot continue to work. When the chiller has a high-pressure alarm, there are the following reasons, which can be dealt with in a targeted manner:
- The cooling water temperature is too high, and the condensation effect is not good
The rated working condition of the cooling water required by the chiller is 30~35°C. The high water temperature and poor heat dissipation will inevitably lead to high condensation pressure. This phenomenon often occurs in high temperature seasons.
Solution: reduce the water temperature (cooling water allows 21°C-38°C)
- Insufficient cooling water flow
The cooling water flow rate is insufficient, the rated water flow rate cannot be reached, the pressure difference between the inlet and outlet water of the unit becomes smaller (compared with the pressure difference at the beginning of the system being put into operation), and the temperature difference becomes larger.
Solution: increase the cooling water flow. Install an exhaust valve at a high place in the pipeline for exhaust; the pipeline filter is clogged or too fine, and the water permeability is limited. A suitable filter should be selected and the filter screen should be cleaned regularly; the water pump is selected to be small and does not match the system.
- Condenser scaling or blockage
Condensed water is generally tap water, which is easy to scale when the temperature is above 30°C, and because the cooling tower is open and directly exposed to the air, dust and foreign matter can easily enter the cooling water system, causing the condenser to be dirty and blocked, and the heat exchange area is small , the efficiency is low, and it also affects the water flow. The performance is that the water pressure difference between the inlet and outlet of the unit and the temperature difference become larger, the temperature of the upper and lower parts of the condenser is very high when touched by hand, and the copper tube of the condenser liquid outlet is hot.
Solution: Clean the condenser copper tube. Regularly backwash the unit, and perform chemical cleaning and descaling if necessary.
- The refrigerant is mixed with air, nitrogen and other non-condensable gases
This kind of situation usually occurs after maintenance and the vacuuming is not complete.
Solution: Drain the air, re-evacuate, and recharge with refrigerant.
- False alarms caused by electrical faults
Because the high-voltage protection relay is damp, poor contact or damaged, the electronic board of the unit is damp or damaged, and the communication failure causes false alarms.
Solution: For this kind of false fault, the HP fault indicator light on the electronic board is often off or dimly lit, the manual reset of the high-voltage protection relay is invalid, the computer displays “HP RESET”, or disappears automatically, and the operating current of the compressor is measured to be normal. Pressure is also normal.
Latest News
industrial heater price
46Industrial heaters, essential for various heating processes in manufacturing, chemical, and other industries, exhibit a wide range of prices due to multiple interconnected factors. Understanding these factors is crucial for anyone seeking to eval…
working of chillers
59Chillers are sophisticated devices that utilize the refrigeration cycle to remove heat from a fluid, making them essential for cooling processes, equipment, or spaces across various sectors. Their operation hinges on the ability to transfer heat …
water chiller plant working
68A water chiller plant is a complex system designed to produce chilled water, which acts as a heat transfer medium to cool spaces, machinery, or industrial processes. Its operation is centered on the refrigeration cycle, a continuous process that …
water cooled glycol chiller
55A water cooled glycol chiller is a specialized cooling system designed to maintain low temperatures in various industrial, commercial, and institutional applications. It combines the use of a glycol-water mixture as the heat transfer fluid with a…
loading…
已经是到最后一篇内容了!